ENI GREEN DATA CENTER

UHE (Ultra High Efficient) Data Center

12 Months PUE = 1.179 (*)

(*) PUE Measurement Levels (Green Grid)

  • L3 Measurement Interval: Continuous
  • L3 Total Facility Energy: Utility Inputs
  • L1  IT Equipment Energy: UPS Outputs

 

12M PUE = 1,179  highly significant since:

  • DC located in Italy, at 45°N Lat. (45.100°N – 8.863°E), where Dry Bulb Temperature is ≤ 27°C for max 7000 hours per year;
  • 20 years max DBT = 38.9°C (ASHRAE Handbook);
  • Extreme Max WBT = 27.9°C (ASHRAE Handbook)
  • ASHRAE TC 9.9, Thermal and Contamination Guidelines compliancy
  • Uptime Institute Tier IV compliancy with redundant systems/components
  • Current IT load less than 20% of rated design IT load
  • High accuracy in energy measurements (global accuracy class TA + Instruments = 0,3)
  • Standard IT Equipments (no HW custom designed for energy saving purpose)

 

Performed Activities
MEP Design and Site Supervision, Thermodynamics and CFD simulations
Location
Ferrera Erbognone (PV), Italy
Client
Reorder srl
End user
ENI spa
Type
Data Center
Size
5,200 m² rack room – 30 MW IT Load, 2,000 m² HPC RR (High Performance Computing Rack Room), 3,200 m² SC RR (Standard Computing Rack Room)
Team
Marco Negri (R&D and Scientific Director), Reorder (Scientific and Technical Supervision), Pop Solid (Concept Design), Starching srl (Architectural Design and Site Supervision), Redesco srl (Structural Design and Site Supervision), ENI Servizi (Project Management)
Notes
Direct Free Cooling up to 8.00 kW/m2 for HPC RR Direct Free Cooling up to 6.00 kW/m2 for SC RR
Chronology
2011 (design), 2014 (completed)